3. Mount the circuit board to the back of the 800T devices with the
DeviceNet terminal block oriented toward sealed connector/
conduit hole of enclosure. Use the two screws and plastic
spacers provided (2 sizes provided for different 800T device
depths). Tighten circuit board mounting screws to 14 in-lbs.
4. If you are not using a prewired DeviceNet connector, pull the
DeviceNet cable through the conduit at the top of the enclosure.
Then attach the 6 DeviceNet cable leads to the removable
terminal block connector.
Page 1-7 provides a description of the DeviceNet connections.
SpacersSpacers
Circuit Board Circuit Board
Mounting Screws
Toward sealed connector/
conduit hole of enclosure
ATTENTION
!
Do not connect the DeviceNet network to the
DeviceNet terminal block connector when power
is applied to the network or you may damage
the circuit board or the DeviceNet network.
ATTENTION
!
Use conduit fittings with proper seals on the
DeviceNet cable to maintain a watertight
enclosure.
Removable Terminal
Block Connector
Pin 1
Pin 6
Common
CAN Low
Shield
CAN High
VDC+
E GND