Chapter 5
Creating a Sample Application
5–12
5. Use the ["#][{] arrow keys to move the cursor to row 2, column 1
(6 spaces to the left of the word Gallons).
6. Press [F1] (Display Register).
The screen displays a list of register types.
7. Use the [↓↑] keys to highlight 16 Bit Signed Integer and press [Return].
The 16 Bit Signed Integer Display appears.
8. Use the arrow ["#] and [Return] keys to enter the register data below.
Arrows
indicate
changes
9. After pressing [Return] to enter the last line of register data, press [Esc] to
accept the data.
The data display window shows 5 asterisks (*****) before Gallons
indicating the data register position.
Steps 5 – 9 define the data
register for Gallons.