Wiring Power, Control, and Ground Wiring
Table 1 provides the power, control, and ground wire capacity and the
tightening torque requirements. The power, control, and ground terminals
will accept a maximum of two wires per terminal.
Table 1 Power, Control, Ground Wire Size, and Torque Specifications
Terminal Designations for
Conduit Entrance
As shown in Figure 3, the ArmorStart Distributed Motor Controller contains
terminals for power, control, and ground wiring. Access can be gained by
removing the terminal access cover plate.
Figure 3 ArmorStart Power, Control, and Ground Terminals
Table 2 Power, Control, Safety Monitor, and Ground Terminal Designations
Terminals Wire Size Torque Wire Strip Length
Three-phase
Power
and
Ground
Primary/Secondary
Terminal:
1.5…4.0 mm
2
(#16 …#10 AWG)
Primary Terminal:
10.8 lb•in. (1.2 N•m)
Secondary Terminal:
4.5 lb•in (0.5 N•m)
0.35 in. (9 mm)
Control and Power
1.0 mm
2
…4.0 mm
2
(#18…#10 AWG)
6.2 lb•in
(0.7 N•m)
0.35 in. (9 mm)
Terminal Designations No. of Poles Description
A1 (+) 2 Control Power Input
A2 (-) 2 Control Power Common
PE 2 Ground
1/L1 2 Line Power Phase A
3/L3 2 Line Power Phase B
5/L5 2 Line Power Phase C