Rockwell-automation 57C620 AutoMax Programming Executive Version 3.8 Instrukcja Użytkownika Strona 186

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 185
16Ć2 AutoMax Programming Executive Version 3.x
when a STOPĆALL command is issued by the operator or the system
issues a STOPĆALL. To stop all tasks in the rack, follow the directions
below:
1. From the ON LINE menu, select S" for Stop.
2. The screen will display No task selected" and the option All".
Enter A" to stop all tasks. The Status" field for all tasks will then
show that the tasks are in STOP.
Table 16.1Ć Status of Data in the AutoMax Rack after a
STOPĆALL Command or STOP
ĆALL F
ault





LOCAL tunable variables retained retained retained
LOCAL variables retained reset to 0 N/A
COMMON memory variables
nonĆvolatile
are retained;
others are
reset to 0
N/A N/A
I/O variables (including UDC
dual port memory)
inputs
retained and
updated;
outputs are
reset to 0
inputs
retained and
updated;
outputs are
reset to 0
all I/O is
reset to 0
Input values, including:
Feedback registers
UDC/PMI communication
status registers
UDC Error Log info
retained retained N/A
Output values, including:
Command registers
Application registers
ISCR registers
ScanĆperĆinterrupt register
ScansĆperĆinterrupt counter
reset to 0 reset to 0 N/A
Parameter configuration
variables
N/A retained N/A
UDC test switch information N/A retained N/A
D/A setup configuration N/A retained N/A
Operating system retained retained retained
Przeglądanie stron 185
1 2 ... 181 182 183 184 185 186 187 188 189 190 191 ... 297 298

Komentarze do niniejszej Instrukcji

Brak uwag