AĆ1
Appendix A
Technical Specifications
Ambient Conditions
Storage Temperature: -40 to 85
o
C
-40 to 185
o
F
Operating Temperature: 0 to 60
o
C
32 to 140
o
F
Humidity: 5 to 90% nonĆcondensing
Dimensions:
Height: 11.75 inches (29.8 cm)
Width: 1.25 inches (3.2 cm)
Depth: 7.375 inches (18.7 cm)
Weight: 2 pounds (0.9 kg)
System Power Requirements From the Backplane
+ 5 volts: 1.5 A
+ 12 volts: 30 mA
Maximum Module Power Dissipation
7.5 Watts
Recommended Field Wiring Cable
Belden 9501 or Equivalent
Maximum Recommended Field Wiring Length is Dependent
upon the Transmitters
Terminal Board and Cable Assemblies
M/N 61C547: Panel Mount
M/N 61C548: DINĆRail Mount
Input Channels
Number of Input Channels: 16 singleĆended/8 differential software
configurable on a perĆchannel pair basis
Commons: one analog common shared by all 16 voltage input
channels
Isolation: 2500V from analog common to digital ground
2500V rms for 1 minute