FĆ1
Appendix F
Compatibility with Earlier Versions
Version 61C542 modules are similar in operation to 61C542A modules except for
the input channel update times listed below:
Input Channel Update Times (All times are in milliĆseconds)
Number of
Configured
Channels
Unscaled
Data
Scaled
Data
Square Root of
Scaled Data
60 Hz Line
One 24.5 25.5 27.5
60 Hz Line
Freq. Filter
Ebld
Each Added 19.5 20.5 22.5
Freq. Filter
Enabled
Sixteen 317 333 365
Line Freq.
One 7.5 8 10
Line Freq
.
Filters
Di bl d
Each Added 2.5 3 5
Filters
Disabled
Sixteen 45 53 85
50 Hz. Line
One 28.5 29.5 31.5
50 Hz
.
Line
Freq. Filter
Ebld
Each Added 23.5 24.5 26.5
Freq. Filter
Enabled
Sixteen 381 397 429