The following error codes are displayed (using a pattern of COM ER LEDs) while
the AutoMax RĆNet Processor module performs powerĆup diagnostics:
1 Ć EPROM checksum error
2 Ć Scratchpad RAM failure
3 Ć Dual port memory failure
4 Ć Node number switch setting greater than 250
5 Ć Communication circuit failure
Error codes 1Ć3 and 5 will require replacement of the AutoMax RĆNet Processor
module.
 
The following error codes are displayed if any of the indicated faults are detected:
9 Ć Local watchdog interrupt
10 Ć Software test (negative buffer length detected)
11 Ć Software test (message length=0detected)
12 Ć Unused interrupt detected
13 Ć Attempt was made to access a word on an odd byte (address
error)
14 Ć System watchdog interrupt
15 Ć Bus error (RĆNet module unable to reconstruct where to
execute after unsuccessful attempt to access dual port
memory.)