18 Rockwell Automation Publication IASIMP-QS036A-EN-P - April 2013
Chapter 1 Prepare the PowerFlex 525 Drive Hardware
13. To permanently assign this
configuration to the adapter,
wait for the adapter to appear
in the Relation List panel and
select it.
14. Click Disable BOOTP/DHCP.
When power is cycled, the adapter uses the assigned configuration and does not issue a BOOTP request.
Additional Resources
For a list of additional resources that can assist you when preparing the PowerFlex 525 drive hardware, see
page 10.
IMPORTANT
If you do not click Disable BOOTP/DHCP, on a power cycle, the host controller clears the current IP configuration
and begins sending BOOTP requests again.