Programming Manual Logix5000 Controllers Messages Catalog Numbers 1756-L1, 1756-L55, 1756-L61, 1756-L62, 1756-L63, 1769-L31, 1769-L32C, 1769-L32E,

Strona 2 - Important user information

Chapter 1 Controller messages This diagram shows how the controller processes MSG instructions. Description The controller scans

Strona 3 - Summary of changes

Controller messages Chapter 1 Description The controller scans the MSG instruction. The rung-condition-in for the MSG instruction

Strona 4

Chapter 1 Controller messages The controller has the following limits on the number of connections that you can cache. If you have t

Strona 5 - Table of contents

Controller messages Chapter 1 Term Definition The controller can have 10 to 40 unconnected buffers. • The default number is 10.

Strona 6

Chapter 1 Controller messages To determine or change the number of unconnected buffers, use a MSG instruction. • The range is 10 to

Strona 7 - Studio 5000 environment

Controller messages Chapter 1 Set the number of unconnected buffers As a starting value, set the number of unconnected buffers equ

Strona 8 - Additional resources

Chapter 1 Controller messages Tag Name Type Description UCB_Set MESSAGE Control tag for the MSG instruction. Source_Array SINT

Strona 9 - Controller messages

Controller messages Chapter 1 Write 16-bit integers DINTs from the project Buffer of INTs Data for the device DINT_Array

Strona 10 - Message queue

Chapter 1 Controller messages Example: Write integer values to a PLC-5 controller If Condition_2 = 1 then reset the FAL instruction

Strona 11 - Cache list

Chapter 2 Manage multiple messages You can use ladder logic to send groups of message (MSG) instructions in sequence. • To be processed, each MSG in

Strona 12 - Unconnected buffers

Important user information Read this document and the documents listed in the additional resources section about installation, configuration, and ope

Strona 13 - Guidelines

Chapter 2 Manage multiple messages Restart the sequence If the MSGs in group 2 (last group) are currently enabled (Msg_Group.2 = 1

Strona 14 - Get or set the number of

Manage multiple messages Chapter 2 Send the second group of MSGs If Msg_Group.1 changes from 0 -> 1 then send Msg_2. send Msg

Strona 16 - Convert between INTs and

Chapter 3 Send a message to multiple controllers You can program one message instruction to communicate with multiple controllers. To reconfigure a M

Strona 17

Chapter 3 Send a message to multiple controllers Although not required, it is recommended that you add the communication modules and

Strona 18

Send a message to multiple controllers Chapter 3 2. Create the local_array tag, which stores the data in this controller. Tag Nam

Strona 19 - Manage multiple messages

Chapter 3 Send a message to multiple controllers Store the configuration properties for each controller in an array. Before each exe

Strona 20

Send a message to multiple controllers Chapter 3 Example: Type the path to the remote controller. OR Click Browse and browse

Strona 21

Chapter 3 Send a message to multiple controllers The SIZE instruction: • Counts the number of elements in local_array. • Counts th

Strona 22

Send a message to multiple controllers Chapter 3 The following table explains how to configure the message. On this tab If you w

Strona 23 - Introduction

Summary of changes The following table contains the changes made to this revision. Change Topic Updated sample project folder location. “Introducti

Strona 24 - Define your source and

Chapter 3 Send a message to multiple controllers When the index equals the local_array_length, the controller sends the message to a

Strona 25 - CONFIGURATION data type

A array controller configuration 26 B block transfer guidelines 13 buffer for unconnected messages 12, 14 C cache connection 11 communicate m

Strona 28 - Load the message

Rockwell Automation support Rockwell Automation provides technical information on the web to assist you in using its products. At http://www.rockwell

Strona 30 - Restart the sequence

Table of contents Studio 5000 environment ... 7 Additional resources

Strona 32

Preface This manual shows how to program message (MSG) instructions to and from Logix5000™ controllers. This manual is one of a set of related manu

Strona 33

Preface These documents contain additional information concerning related Rockwell Automation products. Resource Description Industrial Automation W

Strona 34 - Rockwell Automation support

Chapter 1 Controller messages This section describes how to transfer (send or receive) data between controllers by executing a message (MSG) instruct