Rockwell-automation Migrating PanelView Enhanced Terminal Applications Instrukcja Użytkownika Strona 31

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 160
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 30
Publication 2711P-QS001A-EN-P - October 2007 31
Review the Application Conversion Log Chapter 4
"PLC Controlled Audio" alarm control
not supported.
Alarm Configuration The PLC Controlled Audio control has a tag assigned.
FactoryTalk View ME software does not support a PLC
Controlled Audio alarm control so does not convert it.
"PLC Controlled Relay" alarm control
not supported.
Alarm Configuration The PLC Controlled Relay control has a tag assigned.
FactoryTalk View ME software does not support a PLC
Controlled Relay alarm control so does not convert it.
Alarm message "Relay" option not
supported.
Alarm Message Configuration One or more relay flags has been enabled for alarm messages.
FactoryTalk View ME software does not support the triggering
of a relay when an alarm is triggered so will not convert this
feature.
Only one hold time is used for
alarming. "Remote Alarm Operation
Hold Time" not supported.
Alarm Configuration One or more of these controls has a tag assigned:
Silence Alarms to PLC
Clear Window to PLC
QTY/TIME Reset to PLC
Message to PLC
FactoryTalk View ME software supports only one hold time for
alarming and this will be set to the value of the PanelView ’e’
Remote Alarm Ack Control Hold Time. The value of the
PanelView ’e’ Remote Alarm Operation Hold Time does not
convert.
"Remote Alarm Control Delay Time"
not supported.
Alarm Configuration These controls have a tag assigned:
Acknowledge to PLC
Acknowledge Control
Message to PLC
In FactoryTalk View ME software, if the Ack control is assigned
to an alarm trigger, the terminal will immediately set the Ack
control without waiting for a delay time when the alarm is
acknowledged. The Remote Alarm Control Delay Time does not
convert.
Bit Acknowledging of alarms not
supported.
Alarm Configuration The Alarm Acknowledge to PLC option is set to Bit and the
Acknowledge to PLC control has one or more tags assigned.
FactoryTalk View ME software does not support bit
acknowledging of alarms so does not convert the
Acknowledge to PLC tags.
Screen security settings not
converted for <Display Name>.
Secure Screen Configuration A screen has one or more Authorize Operator settings enabled.
Screen security is not converted.
FactoryTalk View ME software does support display security.
Security is configured differently.
RSLinx for FactoryTalk View is not
installed, topics not created.
Communication You need to recreate the shortcut name to the PLC in RSLinx
Enterprise software under Communication Setup.
<PanelView ’e’ Tag Name> converted
to memory tag, as its address is
blank.
Any PanelView ’e’ Remote I/O tag with a blank address is
converted to an HMI memory tag.
Conversion Log Messages
Message Applies to this
PanelBuilder 1400e object
Description
Przeglądanie stron 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36 ... 159 160

Komentarze do niniejszej Instrukcji

Brak uwag