Rockwell-automation Migrating PanelView Enhanced Terminal Applications Instrukcja Użytkownika Strona 88

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 160
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 87
88 Publication 2711P-QS001A-EN-P - October 2007
Chapter 6 Review Unsupported Features and Implement Workarounds for Migration Issues
10. Click the next empty rung.
11. On the tabbed instruction
bar, select the Program
Control tab and click RET.
The RET command exits the
subroutine and returns you
to the MAIN program.
12. Click X an save your
changes.
13. Double-click your main
program file.
14. Click the last rung.
15. On the tabbed instruction
bar, select the Program
Control tab and click JSR.
16. The JSR instruction jumps to
the subroutine that handles
all the visible state MOV
instructions just created.
17. In the JSR subroutine, set
the Prog File Number to the
number specified in the
Program File that handles all
the MOV instructions.
18. Click X to save all changes.