Technical Specifications
A-1
APPENDIX A
Technical Specifications
Table A.1 – Drive Monitoring and Limits
AC Input Overvoltage Trip 570 VAC/690 VAC (480 V/575 V Class)
AC Input Undervoltage Trip 280 VAC/345 VAC (480 V/575 V Class)
Bus Overvoltage Trip 810 VDC/1013 VDC (480 V/575 V Class)
Bus Undervoltage Trip 305 VDC/381 VDC (480 V/575 V Class)
Nominal Bus Voltage 648 VDC/810 VDC (480 V/575 V Class)
All Drives
Heat Sink Thermistor Monitored by microprocessor overtemp trip
Drive Overcurrent Trip
Software Current Limit
Hardware Current Limit
Instantaneous Current Limit
20-150% of rated current
200% of rated current (typical)
220-300% of rated current (dependent on
drive rating)
Line Transients up to 6000 volts peak per IEEE C62.41-1991
Control Logic Noise Immunity Showering arc transients up to 1500V peak
Power Ride-Thru 15 milliseconds at full load
Logic Control Ride-Thru 0.5 seconds minimum, 2 seconds typical
Ground Fault Trip Phase-to-ground on drive output
Short Circuit Trip Phase-to-phase on drive output
Intermittent Overload 110% overload capability for up to 1 minute.
150% overload capability for up to 3 seconds.
Current Limit Capability Proactive Current Limit programmable from
20 to 150% of rated output current.
Independently programmable proportional
and integral gain.
Electronic Motor Overload
Protection
Class 10 protection with speed sensitive
response. Investigated by U.L. to comply with
N.E.C. Article 430. U.L. File E59272, volume
12.