Publication GMC-RM001A-EN-P July 2001
Chapter
4
Shielding Wires, Cables, and Components
Chapter Objectives
This chapter describes how using shielded cable or steel shields can
reduce electrical noise coupling. This chapter covers the following
topics:
Understanding the shielding concept
Ferrite sleeves
Mixing categories
Understanding the
Shielding Concept
You can avoid many of the problems caused by noise by shielding
sources and victims (along with their associated wiring) with the use
of shielded cable or a supplementary steel shield.
If sources and victims cannot be sufficiently segregated it may be
possible to prevent noise coupling by shielding as shown in the figure
below.
Figure 4.1
Wire segregation vs. shield
Dirty Zone
Clean Zone
Minimum segregation is
150 mm (6.0 in.) within a panel
Grounded steel shield
allows minimal segregation
distance.