Publication GMC-RM001A-EN-P July 2001
Chapter
5
Filtering Noise
Chapter Objectives
This chapter describes how low-pass filters and ferrite sleeves can
reduce electrical noise coupling. This chapter covers the following
topics:
Understanding the filtering concept
Filter performance
Ultrasonic transducers
AC line filters
Understanding the Filtering
Concept
If sources and victims are connected by wiring, you can prevent noise
coupling by filtering. Low-pass filters attenuate high frequency noise
without affecting the low frequency signals.
Commercial AC Line Filters for Low Voltage Circuits
Provided that motor cable lengths are short, less than 20 m (60 ft),
commercial AC line filters work well in low voltage circuits. Two-stage
types are preferred.
If motor cable lengths are long, the natural ringing frequency is
typically at too low a frequency (below 300k Hz) to be attenuated by
commercial AC line filters. To determine if your cables are long, refer
to the section Installing Long Motor Cables in Appendix A.