ICS Regent+Plus® PD-7034 Industrial Control Services 1 Isolated Guarded Output Modules 24 to 120 VAC/DC (T7485) Issue 1, March, 06 The Isolated Gua
Isolated Guarded Digital Output Module (T7485) 10 Industrial Control Services Fault Tolerant Configuration with Redundant Actuators When redundant
Isolated Guarded Digital Output Module (T7485) PD-7034 Mar-06 11 In general, each output circuit is rated for 1.5 Amps from 0 to 40º C, derated l
Isolated Guarded Digital Output Module (T7485) 12 Industrial Control Services Resistive Loads If resistive loads are applied, the isolated Guarded
Isolated Guarded Digital Output Module (T7485) PD-7034 Mar-06 13 Fault Mode Jumper The fault mode jumper is located behind the ID switch cover in
Isolated Guarded Digital Output Module (T7485) 14 Industrial Control Services Figure 7. Installing Slot Keys. Configuration Each output module
Isolated Guarded Digital Output Module (T7485) PD-7034 Mar-06 15 1) Set the Module Type: Position the cursor on the module slot you wish to defin
Isolated Guarded Digital Output Module (T7485) 16 Industrial Control Services Figure 9. Defining an Isolated Guarded Digital Output Point. Name
Isolated Guarded Digital Output Module (T7485) PD-7034 Mar-06 17 Output Module Definition In addition to configuring output point definitions, yo
Isolated Guarded Digital Output Module (T7485) 18 Industrial Control Services quarter turn from its locked position releases the fuse holder, exte
Isolated Guarded Digital Output Module (T7485) PD-7034 Mar-06 19 Minimum Load 20 mA Over Voltage Protection Continuous: 450 VAC Output Test Loa
Isolated Guarded Digital Output Module (T7485) 2 Industrial Control Services Two isolated Guarded output modules can be connected in parallel to
Isolated Guarded Digital Output Module (T7485) 20 Industrial Control Services Electromagnetic Interference • IEC 801 Part 2 - Electrostatic Discha
Isolated Guarded Digital Output Module (T7485) PD-7034 Mar-06 3 field programmable gate arrays (FPGA). Each FPGA independently operates one of
Isolated Guarded Digital Output Module (T7485) 4 Industrial Control Services Testing and Diagnostics Automatic testing is performed on the isolat
Isolated Guarded Digital Output Module (T7485) PD-7034 Mar-06 5 performed on each switch to eliminate the effects of AC phase on the test. When
Isolated Guarded Digital Output Module (T7485) 6 Industrial Control Services primary voltage is switched off) a blown fuse will not be detected.
Isolated Guarded Digital Output Module (T7485) PD-7034 Mar-06 7 Figure 3. Isolated Guarded Output Module.
Isolated Guarded Digital Output Module (T7485) 8 Industrial Control Services Shutdown Indicator Upon loss of communications with the controller,
Isolated Guarded Digital Output Module (T7485) PD-7034 Mar-06 9 In a fail-safe configuration, removing the module disables all outputs. Figur