Rockwell-automation T8160 Trusted TMR Interface Instrukcja Użytkownika Strona 47

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 80
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 46
Trusted
TM
TMR Module T8160
Issue 13 May 13 PD-T8160 47
4.25. I/O Complex Equipment ‘SX7446’
Description: T7446 Relay Output Module. The Relay Output Module provides relay outputs for
controlling eight field loads. This board definition is used in a simplex configuration.
Product Description reference: PD-T7017 Relay Output Module
OEM PARAMETERS:
OEM parameter Valid numbers Description
TICS_CHASSIS
TICS_SLOT
1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)
The TICS chassis & slot number where the TMR Interface
module is placed
REGENT_CHASSIS
REGENT_SLOT
1 – 16
1 – 10
The chassis & slot number within the Regent+Plus I/O where the
Module is placed.
CONFIGURATION
PHYSICAL MODULE:
RACK 1: 8 BOOLEAN outputs States to be written to the two modules identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 8 is module channel 8.
TRUE - channel high, FALSE – channel low
RACK 2: 1 BOOLEAN input Input reflecting the board status of the two modules specified.
FALSE - board ok, TRUE – board fault
Notes:
1. All parameters must be supplied, even for virtual boards.
2. Trusted
TM
chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers
start at 1.