Trusted
TM
TMR Module T8160
Issue 13 May 13 PD-T8160 77
5.3. Module Status LEDs
The module status LED states and their meanings are described as follows:
LED State Description
Healthy On Steady Green The Module is healthy.
Flashing Processor sub system slice has failed
Active On Steady Green Module is in the Active state.
Standby On Steady Green Module is in the Standby state.
Educated Off
On Steady Green
Module not educated
Module configuration is valid`.
Green – flashing Module is recognised by the Processor but education is not
complete.
I/O Healthy Off
On Steady Green
I/O sub-system fault
I/O sub-system is healthy
Table 2 Module Status LEDs