Rockwell-automation T8424 Trusted TMR 120Vac Digital Input Module Instrukcja Użytkownika Strona 14

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 29
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 13
Trusted
TM
Module T8424
Issue 8 Sep 11 PD-T8424 14
3. Application
3.1. Module Configuration
There is no configuration required to the physical input module, (i.e. jumpers, etc.). All configurable
characteristics of the module are performed using tools on the EWS and become part of the
a
pplication or system.ini file that is loaded into the TMR Processor. The TMR Processor automatically
configures the input module after applications are downloaded and during Active/Standby changeover.
The IEC1131 TOOLSET provides the main interface to configure the input module. Details of the
configuration tools and configuration sequence are provided in PD-8082B Trusted
TM
Toolset suite.
There are three procedures necessary to configure the input module. These are:
1. Define the necessary I/O variables for the field input data and module status data using the
Dictionary Editor of the IEC1131 TOOLSET.
2. Create an I/O module definition in the I/O Connection Editor for each I/O module. The I/O
module definition defines physical information, e.g. Chassis and Slot location, and allows
variables to be connected to the I/O channels of the module.
3. Using the Trusted
TM
System Configuration Manager, define custom LED indicator modes,
per-channel threshold levels and noise filtering, and other module settings.
3.2. T8424 Complex Equipment Definition
The T8424 I/O Complex Equipment Definition includes 8 I/O boards, referenced numerically by Rack
number:
Rack I/O Board Description Data Type Direction No. of
Channels
1 DI
OEM Parameters - - -
Field Input Status Boolean In 40
2 STATE Field Input State Integer In 40
3 AI Input voltage Integer In 40
4 SPARE Not used Integer - 16
5 LINE_FLT Line Fault Status Boolean In 40
6 DISCREP Channel Discrepancy Integer In 3
7 HKEEPING Housekeeping Registers Integer In 51
8 INFO I/O Module Information Integer In 11
Table 2 Complex Equipment Definition
There are two OEM parameters included in the first rack (DI Board). These OEM parameters define
the primary module position; declaring the modules chassis and slot location. There is no need to
define the secondary module position within the IEC1131 TOOLSET. Where systems may be
required to start-up with a module in the secondary position as the active module, e.g. primary module
is not installed when the application is started, the secondary modules position should be declared in
the module definition of the System Configuration Manager.