Module T8424
Issue 8 Sep 11 PD-T8424 7
Figure 2 shows a simplified functional block diagram of the Trusted
TM
TMR 120VAC Digital Input
Module.
Figure 2 Functional Block Diagram
1.1. Field Termination Unit (FTU)
The Field Termination Unit (FTU) is the section of the I/O module that connects all three FIUs to a
single field interface. When installed in a Trusted
TM
Controller or Expander Chassis, the FTU field
connector interconnects to the I/O cable assembly attached at the rear of the chassis.
The SmartSlot link is passed from the HIU to the field connections via the FTU. These signals go
directly to the field connector and maintain isolation from the I/O signals on the FTU. The SmartSlot
link is the intelligent connection between active and standby modules for co-ordination during module
replacement.
FTA
Input
Field
D
evice
Field Termination Unit (FTU)
SLICE A
I
MB A
FRONT PANEL
A/D
CONVERTER
FIELD LOGIC
CONTROL
ISOLATION BARRIER
SLICE POWER
SUPPLY
HOUSEKEEPING
FIU
S
LICE CONTROL A
T
IME STAMP
BUS INTERFACE
H
OUSEKEEPING
MODULE TEMP
SUPPLY DIAG
DSP REFERENCE
REDUNDANT
SUPPLY
24V1 24V2
HIU POWERFIU POWER
FRONT PANEL
V
OTING LOGIC
SLICE B
S
LICE C
SERIAL DISPLAY LATCHES
VOTED STATUS DISPLAY LEDs
HEALTH
INDICATORS
SLICE B
SLICE C
IMB B
IMB C
HIU
VAC