14 POINT I/O™ 5V and 24V Encoder/Counter Modules
Publication 1734-IN005G-EN-E - September 2012
The Encoder/Counter Module uses several words to communicate real-time input and
output data as well as non-real time module information, that is, description, revision, and
configuration. This shows the words that you can exchange. You can read (get) or write
(set) data using an Explicit Message.
Filter Selection
(1)
07 06 05 04 03 02 01 00
0ZFBFAFFS
0000No filter
000150 kHz (10 μs + 0 μs/-1.6 μs)
00105 kHz (100 μs + 0 μs/-13.2 μs)
0100500 Hz (1 ms + 0 μs/-125 μs)
100050 Hz (10 ms + 0 ms/-1.25 ms)
0 A input not filtered
1 A input filtered
0 B input not filtered
1 B input filtered
0 Z input not filtered
1 Z input filtered
(1)
Assumes a 50% duty cycle signal.
Scalar Selection
07 06 05 04 03 02 01 00 Scalar
(1)
00000001Z F
min
= 0.149 Hz
00000 010Z/2 F
min
= 0.298 Hz
00000100Z/4 F
min
= 0.596 Hz
00001000Z/8 F
min
= 1.192 Hz
00010000Z/16 F
min
= 2.384 Hz
0010 0000Z/32 F
min
= 4.768 Hz
01000000Z/64 F
min
= 9.537 Hz
10000000Z/128 – F
min
= 19.073 Hz
(1)
Where F
min
indicates the frequency at which the zero frequency detect is asserted due to counter overflow.
Przeglądanie stron 13