Rockwell-automation 1734-IK/C POINT I/O 5V and 24V Encoder/Counter Mod Instrukcja Użytkownika Strona 15

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 24
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 14
POINT I/O™ 5V and 24V Encoder/Counter Modules 15
Publication 1734-IN005G-EN-E - September 2012
Assemblies
Instances
(Dec/Hex)
Services Field Bytes
#101 (0x65) Get Present channel data 4
Status 2
#102 (0x66) Get Stored channel data 4
Status 2
#103 (0x67) Get Present channel data 4
Stored channel data 4
Status 2
#104 (0x68) Get Programming error code 2
#105 (0x69) Set/Get Counter control 1
#106 (0x6a) Set/Get Counter configuration 1
Filter selection 1
Decimal position 1
Reserved 1
Time base 2
Gate interval 1
Scalar 1
Rollover value 4
Preset value 4
Counter control SSV 1
#123 (0x7b) Set/Get Counter configuration 1
Filter selection 1
Decimal position 1
Reserved 1
Time base 2
Gate interval 1
Scalar 1
Rollover value 4
Preset value 4
Counter control SSV 1
Alignment (reserved = 0) 1
Przeglądanie stron 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 ... 23 24

Komentarze do niniejszej Instrukcji

Brak uwag