ArmorPoint I/O Modules with 8 Configurable 24V DC Points 13
Publication
1738-IN026B-EN-E - February 2010
Network status Off Device is not online:
- Device has not completed
dup_MAC-id test.
- Device not powered – check module
status indicator.
Green Device is online and has one or more
I/O connections in established state
Flashing green Device is online but has no connections
in established state
Flashing red One or more I/O connections in
timed-out state
Red Critical link failure – failed
communication device. Device detected
error that prevents it from
communicating on the network.
Flashing red/green Communication faulted device – the
device has detected a network access
error and is in communication faulted
state.
Device has received and accepted an
Identity Communication Faulted
Request – long protocol message.
I/O status Off I/O is inactive
Yellow I/O is active and under control
Flashing yellow I/O is in charging state
1738-8CFGM8, 1738-8CFGM12, 1738-8CFGM23 Indicator Status
Status Description