16 ArmorPoint I/O Modules with 8 Configurable 24V DC Points
Publication
1738-IN026B-EN-E - February 2010
Environmental Specifications
Attribute Value
Temperature, operating IEC60068-2-1 (Test Ad, Operating Cold),
IEC60068-2-2, (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...60 °C (-4...140 °F)
Temperature,
nonoperating
IEC60068-2-1 (Test Ad, Non-operating Cold),
IEC60068-2-2, (Test Bd, Non-operating Dry Heat),
-40...85 °C (-40...185 °F)
Vibration IEC 60068-2-6 (Test Fc, Operating): 5g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50g
Operating voltage 11...30V DC
Emissions CISPR 11: Group 1, Class A
ESD immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 30…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4:
±3 kV at 5 kHz on signal ports
Surge transient
immunity
IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from 150 kHz...80 MHz