
ArmorPoint I/O Modules with 8 Configurable 24V DC Points 9
Publication
1738-IN026B-EN-E - February 2010
1738-8CFGM23
Communicate with Your Module
Read this section for information about how to communicate with your
module.
I/O messages are sent to (consumed) and received from (produced) the
POINT I/O modules. These messages are mapped into the processor’s or
scanner’s memory. Each module produces 1 byte of input data and consumes
1 byte of I/O data (scanner Tx).
In RSLogix5000, the default tag will be AdapterName:SlotNumber:I.Data.
The data type is a SINT.
Default Data Map – Product Assembly Instance 4
Message Size: 1 Byte
76543210
Data Pt 07 Pt 06 Pt 05 Pt 04 Pt 03 Pt 02 Pt 01 Pt 00
Where: Pt = state of the input point
(view into connector)
Pin 1 - I/O 0
Pin 2 - I/O 1
Pin 3 - I/O 2
Pin 4 - I/O 3
Pin 5 - I/O 4
Pin 6 - I/O 5
Pin 7 - I/O 6
Pin 8 - I/O 7
Pin 9 - Return (Com)
Pin 10 - Return (Com)
Pin 11 - 24V DC
Pin 12 - Chassis
43681
Komentarze do niniejszej Instrukcji