78 Rockwell Automation Publication 1734-UM017B-EN-P - October 2013
Chapter 6 Troubleshoot the Adapter
Status Indicators for ArmorPOINT I/O Adapters
The following describes the status indicators on the 1738-AENTR.
1738-AENTR
Series B
EtherNet I/P
Adapter
Status
Network
Activity
Network
Status
PointBus
Status
System
Power
Adapter
Power
conformance tested
PWR
IP ADDRESS
Link 2
Activity/
Status
Link 1
Activity/
Status
44830
Link 1 Activity/Status
Link 2 Activity/Status
Adapter Status
Network Activity
Network Status
System Power
Adapter Power
POINTBus Status
Status Indicators for 1738-AENTR Adapter
Indicator State Description
Adapter Status Off No power applied to device
Flashing green Device needs commissioning due to missing, incomplete, or incorrect
configuration.
Solid green Device operating normally
Flashing red Recoverable fault:
Complete firmware update
Verify address switches.
Solid red Unrecoverable fault:
Self-test failure (checksum failure, RAM test failure at cycle power)
Firmware fatal error).
Flashing red/green Device is in self-test
Network Activity Off No link established with Port 1 or Port 2.
Flashing green Transmit or receive activity present on Port 1 and/or Port 2 at 100 Mbps.
Transmit or receive activity present on Port 1 and/or Port 2.
One port at 100 Mbps and one port at 10 Mbps.
Solid green Link established with Port 1 and/or Port 2 at 100 Mbps.
Link established with Port 1 and Port 2.
One port at 100 Mbps and one port at 10 Mbps
Flashing yellow Transmit or receive activity present Port 1 and/or Port 2 at 10 Mbps.
Solid yellow Link established with Port 1 and/or Port 2 at 10 Mbps.