1 Publication 1746-6.1.2 - July 2000
Chapter
3
Planning Hardware Installation
This chapter provides guidelines regarding your hardware installation
and includes the following topics:
Understanding general wiring practices
Routing wires
Classifying your conductors
Placing your SLC Servo Module
Refer to your SLC 500 documentation for more information on these
topics.
General Wiring Practices
General wiring practices include:
Using shielded cables
Routing wires
Using Shielded Cables
For many connections, we recommend shielded cable. Using shielded
cables and properly connecting their shields to ground protects
against electromagnetic noise interfering with signals transmitted
through the cables.
Within a cable, pairs of wires are twisted together. Using a twisted pair
for a signal and its return path provides further protection against
noise.
Shield wires should be terminated at one end only. The termination
panel is a convenient place to connect all shield wires while providing
the necessary ground connection.
ATTENTION
!
To avoid personal injury or equipment damage
caused by unpredictable axis motion in your system,
use shielded cable as directed in this manual.