Publication 1746-UM026A-EN-P - September 2003
5-4 I/O Data and Status Information
Input Status Words
Channel Input Status Word 1 (Class 1 and Class 3)
Words 0 through 7 of the input image file (addresses I:e.0 through
I:e.7) reflect the configuration and status of each channel. Use the data
provided in these status words to determine various channel
conditions. Input Status 1 addressing and bit definitions are shown in
the following figures:
Figure 5.3 Input Status 1
Input Image Words 0 through 7 Function
Input Status 1
Class 1 and Class 3
I:e.0 Channel 0
I:e.1 Channel 1
I:e.6 Channel 6
I:e.7 Channel 7
Table 5.3 Input Status 1 Word Details
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Output channel disable
Output channel enable
0
1
1746-NO8V Output Ranges:
±10V dc
1 to 5V dc
0 to 5V dc
0 to 10V dc
0
0
1
1
0
1
0
1
1746-NO8I Output Ranges:
0 to 21 mA
4 to 20 mA
0 to 20 mA
Invalid
0
0
1
1
0
1
0
1
Invalid 0
1746-NO4 compatible format
Engineering units
Scaled for PID
Proportional counts
User-defined scale
Invalid
Invalid
Invalid
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
Invalid 0 0 0 0 0
24V Power Failure 1
Current Loop Open 1
Module/SLC Resetting 1
Fatal Channel Error 1