Publication 1746-UM026A-EN-P - September 2003
5-6 I/O Data and Status Information
Channel Input Status Word 2 (Class 3 Only)
Words 8 through 15 of the input image file (addresses I:e.8 through
I:e.15) reflect the parameter options, fault settings, and alarm options
for each channel. Input Status 2 addressing and bit definitions are
shown in the following figures:
Figure 5.4 Input Status 2
Input Image Words 0 through 7 Function
Input Status 2
Class 3
I:e.8 Channel 0
I:e.9 Channel 1
I:e.14 Channel 6
I:e.15 Channel 7
Table 5.4 Input Status 2 Word Details
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
User Scaling Values Set 1
Clamping Values Set 1
Limit Alarm Values Set 1
Ramping/Rate Limiting Values Set 1
Preset Fault Value Set 1
Reset Output on Fault 1
Hold Output on Fault 1
Preset Output on Fault 1
Alarms Will Be latched 1
Output at Low Clamp Alarm 1
Output at High Clamp Alarm 1
Low Limit Alarm 1
High Limit Alarm 1
Under Range Alarm 1
Over Range Alarm 1
Channel Configuration Error 1