Setting Up the Hardware
Publication
1746-6.18 April 1998
Module outputs connect to a separate 2-conductor output terminal
block located beneath the input terminal block.
1746-QV
Output
Terminal Block
Analog Output
("
10v dc)
Dif
f.
Input
Outputs
to valves
Servo Amplifier
(Proportional)
(+)
(–)
T
o solenoid A
T
o solenoid B
A
B
+24V dc PS
0V dc PS
2
1
0V
Important:
Ground the shield of the amplifier
output cable to a 0V connection in the amplifier
.
Do not connect the shield to earth ground.
Note: Follow manufacturer recommendations for shielding the output
cables of the proportional amplifier. Typically, pulse-width modulated
outputs radiate electrical noise originating from the +24V dc power
supply, so isolate the shields of the amplifier output cable to a 0V dc
connection inside the proportional amplifier.
You have a choice of three configurations to match your hydraulics:
proportional amplifier with ramp and proportional valve
servo amplifier with ramp and variable-volume pump
Allen-Bradley 1305 Drive and hydraulic pump
You may use either of the following output voltage ranges:
0-10V dc for the Allen-Bradley 1305 Drive or variable-volume pump
–10 to +10V dc for the proportional amplifier and proportional valve
Important: Signals in this type of control system are very susceptible
to radiated electrical noise. The module is designed to set the loss-of-
sensor bit I:e.0/8 and the LDT-error bit I:e.0/0 when it detects position
values that are lost or corrupted by electrical noise.
Connect module output terminals to output devices with correct bonding:
connect power supply output commons together
electrically isolate power supply output commons from earth ground
use bond wires that are equal in size to signal wires
Minimize interference from radiated electrical noise with correct
shielding and grounding:
connect all of the following to earth ground:
– LDT flange, frame, and machine
– I/O chassis
– protective ground
– AC ground
– cable shields at one end only, preferably with 3/8” braid wire
(for analog output, "15V dc PS, 24V dc PS, and LDT)
– terminal 4 of the input terminal block
Connect Module Outputs
to Output Devices
Minimizing Interference
from Radiated Electrical
Noise