Publication 1753-PM001A-EN-P - November 2005
Connect to the GuardPLC Controller 1-7
The RSLogix Guard PLUS! Hardware Management window opens.
Both the Project Management and Hardware Management windows
are normally open when running RSLogix Guard PLUS! software.
Step 3: Configure the Controller Type and SRS
To go online, you must specify the controller type and change the
default SRS. The software defaults to an SRS of zero (0), which is the
only illegal SRS value. To accept the controller type, the SRS must be
changed to a value between 2
(1)
and 65535.
1. Expand the project tree in the Hardware Management window
until [0] Resource is visible.
2. Right-click [0] Resource and choose Properties.
(1) The programming terminal defaults to 1.