Chapter
2
Connect to GuardPLC Distributed I/O Modules
In This Chapter
This chapter guides you through the process of addressing,
configuring, and connecting to the distributed I/O modules. GuardPLC
distributed I/O modules are ‘owned’ by a GuardPLC controller. This
allows the parent controller to connect signals to the inputs and
outputs of the distributed I/O modules the same way that signals are
connected to the controller’s local I/O.
Understand Module
Addressing
Module Default Settings
The out-of-box settings for a GuardPLC distributed I/O module are
shown in the table below.
SRS (System.Rack.Slot)
The SRS of the parent controller is always xxxxx.0. For example, the
default SRS of a GuardPLC controller is 60000.0. If you change the SRS
to 25, the actual SRS of the controller is 25.0.
For this information See page
Understand Module Addressing 2-1
Add the Module to the Hardware Configuration 2-2
Configure the Module 2-3
Go Online With the Module 2-5
Parameter Setting
IP Address 192.168.0.99
Subnet Mask 255.255.252.0
SRS
(1)
(1) The SRS code is compiled with the program.
60000.1