112Rockwell Automation Publication 1756-UM010B-EN-P - December 2011
112 Configuring the Configurable Flowmeter Module
C.Ch0LowFreqClear Decimal BOOL Enables the minimum detectable frequency
level for Channel 0.
Set the bit to 1 to enable it
1
C.Ch0PreTrigger Decimal BOOL Enables the PreTrigger on Channel 0 for full
flow.
Set the bit to 1 to enable it
1
C.Operations[0].FillMode Decimal SINT Sets the Trickle mode to complete on fill total
target or time.
0 = Fill total target (Engineering units)
1 = Time (seconds)
0
O.OutputControl[0].0 Decimal BOOL Manually sets the operation of outputs
connected to channel 0.
0 = Module operation of outputs
1 = Override Output0 to 0
2 = Override Output0 to 1
0
O.Total[0].FillEnable Decimal BOOL Enables the filling operation on output
connected to channel 0.
0 = Fill operation is disabled
1 = Fill operation is enabled.
0
O.Total[0].FillStart Decimal BOOL Begins filling operation when Fill Enable is
enabled on output connected to channel 0.
0 = Do not begin filling
1 = Begin filling
0
O.Total[0].FillHold Decimal BOOL Holds/pauses filling operation on output
connected to channel 0
0 = Continue filling operation
1 = Hold/pause filling operation
0
O.Total[0].FillTotalTarget Float REAL Target for Fill Complete, except when Fill
Transition is greater than this value.
100
O.Total[0].FillTransition Float REAL When fill cycle is started, trickle flow is
initiated when the Fill Total is equal to or
greater than this value. Full flow is initiated
when the Fill Total is less than this value.
75
O.Total[0].FillTransitionTimer Float REAL When timed trickle flow is selected, the
status remains ON for this time during this
state.
The value must be changed prior to entering
the trickle flow state.
1.0
O.Total[0].Overrange Decimal BOOL Enables the Overrange alarm on output
connected to channel 0. When the Frequency
Period exceeds 100KHz, this alarm is set.
0 = No Alarm
1 = Alarm Enabled
0
Table 9 - Tag Changes Required for Totalizer Mode Using Filler Function