149Rockwell Automation Publication 1756-UM010B-EN-P - December 2011
Configure Output Behavior with RSLogix 5000 Version 16 and Earlier 149
Copy and Paste the Tags and Logic from the Example to Your Program
1. Minimize the CFM_DEMO project and open a new instance of
RSLogix 5000 software.
2. Open CFM_GenericProfileExample.ACD.
3. In the controller organizer of the CFM_GenericProfileExample project,
expand the User-Defined data types.
4. Copy one of the User-Defined data types.
You must select and copy each of the User-Defined data types
individually.
5. In the CFM_DEMO project, paste the copied User-Defined data type
into the User-Defined data type folder.
6. Repeat steps four and five until all of the User-Defined data types
contained in the CFM_GenericProfileExample project have been pasted
in the CFM_DEMO project.