46 PLC-5 Ethernet Interface Module
Publication 1785-IN019B-EN-P - January 2007
Environmental Specifications
Attribute Value
Operating Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0...60
o
C (32...140
o
F)
Storage Temperature IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bc, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
–40...85
o
C (–40...185
o
F)
Relative Humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...90% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10...500 Hz
Shock, Operating IEC 60068-2-27 (Test Ea, Unpackaged shock):
30 g
Shock, Nonoperating IEC 60068-2-27 (Test Ea, Unpackaged shock):
50 g
Emissions Group 1, Class A (with appropriate enclosure)
ESD Immunity IEC 61000-4-2:
6 kV indirect contact discharges
Radiated RF Immunity IEC 61000-4-3:
10V/M, with 1 kHz sine-wave 80% AM from 80...2000 MHz
10V/M with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/M with 200 Hz 50% Pulse 100% AM at 1890 MHz
EFT/B Immunity IEC 61000-4-4:
+
2 kV at 5 kHz on shielded communications ports
+
1 kV at 5 kHz on unshielded communications ports
Surge Transient Immunity IEC 61000-4-5:
+
2 kV line-earth (CM) on communications ports
Conducted RF Immunity IEC 61000-4-6:
10V rms with 1kHz sine-wave 80% AM from 150 kHz...80 MHz
Enclosure Type Rating None (open style)