5. If need to troubleshoot Status Register tags, use the following
table as a reference to interpret module or network status.
Status Register Tag Values
If Tag Member Displays
Value
Then Status Is
Run 0 Scanner in idle mode.
Run 1 Scanner in run mode.
Fault 0 Scanner not faulted.
Fault 1 Scanner faulted.
DisableNetwork 0 Scanner not disabled.
DisableNetwork 1 Scanner disabled.
DeviceFailure 0 Scanner communicating with all devices.
DeviceFailure 1 Scanner not communicating with at least 1 device.
AutoVerify 0 Data size of each device matches the amount of
memory allocated for the device in the scanner.
AutoVerify 1 Data size of at least 1 device does not match the
amount of memory allocated for the device in the
scanner.
CommFailure 0 No network-wide communication problem exists
CommFailure 1 Network-wide communication problem exists
DupNodeFail 0 Scanner is on the network at a unique address
DupNodeFail 1 Scanner is trying to get on the network at an
address that is already in use.
DnetPowerDetect 0 Network connector of the scanner has power.
DnetPowerDetect 1 Network connector of the scanner does not have
power.