10 Ethernet-to-DeviceNet Linking Device
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Connect the Linking Device to the DeviceNet Network
1. Make sure a computer running RSNetWorx for DeviceNet software is
connected to the EtherNet/IP network.
2. With power to the linking device off, connect the DeviceNet network
cable to the DeviceNet connector on the linking device.
The female terminal block connector is provided with the linking
device.
3. Connect the power cable to the linking device.
The female terminal block connector is provided with the linking
device.
ATTENTION:
Do not wire more than 2 conductors on any single terminal.
To comply with the CE Low Voltage Directive (LVD), this equipment must be
powered from a source compliant with Safety Extra Low Voltage (SELV) or
Protected Extra Low Voltage (PELV).
To comply with UL restrictions, this equipment must be powered from a source
compliant with Class 2 or Limited Voltage/Current.
(Red) Net Power 24V DC
(White) CAN High +
CAN Shield
(Blue) CAN Low
(Black) Net Power 24V DC Common