DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 17
Publication
1790-IN006C-EN-P - May 2006
Cable Break Procedures
A cable break in any location between either of the following
produces data of 1 in the data table for all inputs down stream of the
cable break.
Base and digital input expansion module
Digital input expansion module and another digital input
expansion module
Solid Green The module is operating in a normal
condition, and the module is online with
connections in the established state. As
a group 2 module, the module is
allocated to a master.
None.
Flashing
Green
The module is online with no
connections in the established state.
Establish connections to other
nodes. As a group 2 module,
allocate the module to a
master.
Off No power. Wait until the module has
completed the dup_MAC_id
test or power the module.
Function LED Color Module Illumination Condition
I/O Status
Outputs Each output:
Green
None
Green
Output is not energized.
Output is energized.
Inputs Each input:
Green
None
Green
No valid input is present.
Valid input is present.
Indication Probable Cause Recommended Action