ArmorBlock is a trademark of Allen-Bradley Co. Inc.
Publication 1792-5.4 – October 1996
 
Cat. No. 1792-OB4E Series B
To: See page:
Install
the ArmorBlock
Module
3
Connect the Wiring to the ArmorBlock Module
8
Communicate with Y
our ArmorBlock Module
10
Configure Y
our ArmorBlock Module Of
fline Using the DeviceNet
Manager Configuration T
ool
11
Configure Y
our ArmorBlock Module Online Using the DeviceNet
Manager Configuration T
ool
18
Reset Faults 26
Configure Y
our ArmorBlock Module with EDS Files
29
For this reference information
See page:
Default Configuration
14
Status indicators
34
Troubleshooting 34
Specifications 35
This 1792 ArmorBlock I/O block module (Cat. No. 1792-OB4E)
contains I/O circuits, a built-in power supply, and a built-in DeviceNet
I/O adapter. Because of its sealed housing, this 1792 I/O block requires
no enclosure. It is compatible with PLC or SLC programmable
controllers using DeviceNet scanners. The I/O values are accessible
from the PLC or SLC programmable controller data table.
This ArmorBlock module has no switches to set. You set module
parameters using the DeviceNet Manager Software (cat. no.
1787-MGR) or similar configuration tool.
Installation Instructions
Przeglądanie stron 0
1 2 3 4 5 6 ... 35 36

Podsumowanie treści

Strona 1 -  

ArmorBlock is a trademark of Allen-Bradley Co. Inc.Publication 1792-5.4 – October 1996 Cat. No. 1792-OB4E Series BTo: See pa

Strona 2 - ArmorBlock 4 Output Module2

ArmorBlock 4 Output Module10Publication 1792-5.4 – October 1996Communicate with Your ArmorBlock ModuleThis ArmorBlock module acts as a slave in a mas

Strona 3 - 1770-KFD

11 ArmorBlock 4 Output ModulePublication 1792-5.4 – October 1996Configure Your Armor Module Offline Using theDeviceNet Manager Configuration Tool

Strona 4 - • set the data rate

ArmorBlock 4 Output Module12Publication 1792-5.4 – October 1996Adding a Device to the NetworkAction ResponseAt the network screen, click on the“add d

Strona 5 - Set new node

13 ArmorBlock 4 Output ModulePublication 1792-5.4 – October 1996Configure your Device ParametersAfter adding the devices to the network, you must conf

Strona 6 - Mount the ArmorBlock Module

ArmorBlock 4 Output Module14Publication 1792-5.4 – October 1996Configuring the ParametersDefault settings for the 4 output module are:autobaud when e

Strona 7 - Mounting Dimensions

15 ArmorBlock 4 Output ModulePublication 1792-5.4 – October 19962. Click on the radio button to select a different setting. To save thesetting, clic

Strona 8 - • the DeviceNet connector

ArmorBlock 4 Output Module16Publication 1792-5.4 – October 1996Saving to a File1. To save those parameters to a file, click on the button.You see th

Strona 9 - Connecting the Output Wiring

17 ArmorBlock 4 Output ModulePublication 1792-5.4 – October 1996Printing to a Text File1. If you choose to save your changes to a text file, click on

Strona 10

ArmorBlock 4 Output Module18Publication 1792-5.4 – October 1996Configure Your Armor Module Online Using theDeviceNet Manager Configuration ToolT

Strona 11 - Configure

19 ArmorBlock 4 Output ModulePublication 1792-5.4 – October 19963. After setting the parameters, click on the button. Thesystem will automatically

Strona 12

ArmorBlock 4 Output Module2Publication 1792-5.4 – October 1996European Union Directive ComplianceIf this product is installed within the European Uni

Strona 13 - The software displays

ArmorBlock 4 Output Module20Publication 1792-5.4 – October 1996Add the Device to the NetworkAction ResponseAt the network screen, click on the“add de

Strona 14 - The parameter screen appears

21 ArmorBlock 4 Output ModulePublication 1792-5.4 – October 19964. Click once on the device you wish to configure on the project screenand choose .Th

Strona 15

ArmorBlock 4 Output Module22Publication 1792-5.4 – October 19965. Load parameters.If you want to load parameters ChooseFrom a fileYou see this screen

Strona 16 - ArmorBlock 4 Output Module16

23 ArmorBlock 4 Output ModulePublication 1792-5.4 – October 19966. Modify the parameter.If you want to ChooseModify a parameterYou see a screen simila

Strona 17 - Online Help

ArmorBlock 4 Output Module24Publication 1792-5.4 – October 19967. Save parameters to a file, to the device, or print to a file.If you want to ChooseS

Strona 18

25 ArmorBlock 4 Output ModulePublication 1792-5.4 – October 1996Monitoring Parameters OnlineYou can monitor parameters at the Device Configuration scr

Strona 19

ArmorBlock 4 Output Module26Publication 1792-5.4 – October 1996Reset FaultsThere are various ways to reset faults on an ArmorBlock module.• cycle pow

Strona 20 - Add the Device to the Network

27 ArmorBlock 4 Output ModulePublication 1792-5.4 – October 1996The device configuration screen appears. Select the Reset Faulted I/Oparameter.After s

Strona 21

ArmorBlock 4 Output Module28Publication 1792-5.4 – October 1996Reset Faults using Explicit Message Program ControlYou can also reset outputs using th

Strona 22 - 5. Load parameters

29 ArmorBlock 4 Output ModulePublication 1792-5.4 – October 1996Configure Your Armor Module Using EDS FilesCurrent versions of DeviceNet Manager

Strona 23 - 6. Modify the parameter

3 ArmorBlock 4 Output ModulePublication 1792-5.4 – October 1996Install Your ArmorBlock ModuleInstallation of the ArmorBlock module consists of:• setti

Strona 24

ArmorBlock 4 Output Module30Publication 1792-5.4 – October 1996”This connection contains status from outputs at bits 0–3.”;Output1 =1, $ The size in

Strona 25 - Parameters Online

31 ArmorBlock 4 Output ModulePublication 1792-5.4 – October 1996”Fault State”, $ Parameter Name””, $ Units String$$$$$$$$$$ Help string $$$$$$$$$$$”De

Strona 26 - Reset Faults

ArmorBlock 4 Output Module32Publication 1792-5.4 – October 1996$ Value is gettable only. $ Enumerated strings are supported.8, $ Data Type – unsigned

Strona 27

33 ArmorBlock 4 Output ModulePublication 1792-5.4 – October 19966, $ Link Path Size”20 09 24 04 30 04”, $ Link Path to Output 4 status attribute.0x003

Strona 28 - Word Input Fault

ArmorBlock 4 Output Module34Publication 1792-5.4 – October 1996Troubleshoot with the IndicatorsThe ArmorBlock I/O module has 2 types of indicators:•

Strona 29

35 ArmorBlock 4 Output ModulePublication 1792-5.4 – October 1996Specifications4 Output Module – 1792-OB4E/BOutput SpecificationsOutputs per Block 4 so

Strona 30

ArmorBlock 4 Output Module36Publication 1792-5.4 – October 19964 Output Module – 1792-OB4E/BEnvironmental ConditionsOperational TemperatureStorage Te

Strona 31

ArmorBlock 4 Output Module4Publication 1792-5.4 – October 19962. Using DeviceNet Manager Software, go online using the “SetupOnline Connection” selec

Strona 32

5 ArmorBlock 4 Output ModulePublication 1792-5.4 – October 19965. The bar at the bottom of the screen will tell you when you go online.6. At the utili

Strona 33

ArmorBlock 4 Output Module6Publication 1792-5.4 – October 1996Mount the ArmorBlock ModuleMount the block module directly to the machine or device. Co

Strona 34 - • Mod/Net status indicator

7 ArmorBlock 4 Output ModulePublication 1792-5.4 – October 1996Mounting Dimensions6.242.632.57.741.903.0554 mounting holesfor #10 screws(77.6)(48.3)(1

Strona 35 - Specifications

ArmorBlock 4 Output Module8Publication 1792-5.4 – October 1996Connect the Wiring to the ArmorBlock ModuleThe block module uses quick disconnect, scre

Strona 36 - Worldwide representation

9 ArmorBlock 4 Output ModulePublication 1792-5.4 – October 1996Connecting the Output WiringConnect individual output wiring to micro connectors which