Rockwell-automation 1792-OB4E INSTL.INST ARMORBLOCK 4 OUTPUT Instrukcja Użytkownika Strona 26

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 36
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 25
ArmorBlock 4 Output Module26
Publication 1792-5.4 – October 1996
Reset Faults
There are various ways to reset faults on an ArmorBlock module.
cycle power to the module by disconnecting, then reconnecting the
DeviceNet connector
use the Reset Faulted I/O feature on the parameter screen
use the explicit message program control feature
disconnect, then reconnect output power connector
!
ATTENTION: If you reset a fault by removing and
replacing the output power connector, outputs
(including the faulted output) will be on when power
is reconnected.
Reset Faults Online Using the Parameter Screen
To reset faults online, return to the network screen and proceed as
follows:
1.Click on the faulted device.
2.Then click on the Configure
Device button.
Przeglądanie stron 25
1 2 ... 21 22 23 24 25 26 27 28 29 30 31 ... 35 36

Komentarze do niniejszej Instrukcji

Brak uwag