Rockwell-automation 1792-OB4E INSTL.INST ARMORBLOCK 4 OUTPUT Instrukcja Użytkownika Strona 35

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 36
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 34
35
ArmorBlock 4 Output Module
Publication 1792-5.4 – October 1996
Specifications
4 Output Module – 1792-OB4E/B
Output Specifications
Outputs per Block 4 sourcing
Output Voltage Range 19 – 30V dc
On-state Voltage Maximum 0.25V dc @ rated current
On-state Current Maximum 2.0A per output @ 60
o
C
1.0A per output @ 70
o
C
Module Current (all outputs on)
Maximum
8.0A per module
1
Off-state Leakage Current Maximum 1.5mA per output
Surge Current Maximum 4.0A for 10ms, repeatable every 2s
Indicators Mod/Net Status – red/green
I/O Status – yellow/red (customer field side
driven)
General Specifications
DeviceNet Power Voltage
Current
11.0 – 25.0V dc
100mA
Surge Current at Power Up Less than 10A for 5ms
Dimensions Inches
Millimeters
2.6H X 7.7W X 3.06D
66H X 195W X 77.7D
Connectors 1792-OB4EA/B – Aluminum connectors
1792-OB4ES/B – Stainless Steel Connectors
Power Dissipation Maximum 4.0 Watts
Thermal Dissipation Maximum 13.7 BTU/hr
Isolation 500V ac – outputs to DeviceNet
Specifications continued on next page
Przeglądanie stron 34
1 2 ... 30 31 32 33 34 35 36

Komentarze do niniejszej Instrukcji

Brak uwag