10 FLEX Ex Frequency Input Module
Publication
1797-5.9 - June 2010
Relay Connections
Type of Input
Channel 0 Terminations
4
Channel 1 Terminations
4
Power Input
GND
5
Power
Input
1
GND
5
Frequency
NAMUR Proximity
1
76 8 9
Contact Switch
2
76 8 9
500 mV ac Magnetic Pickup 5 3 10 12
50 mV ac Magnetic Pickup
3
5 3 10 12
6V ac Vortex 2 1 3 13 14 12
3V ac Vortex 2 0 3 13 15 12
Gate
NAMUR Proximity
1
24 23 25 26
Contact Switch
2
24 23 25 26
500 mV ac Magnetic Pickup 22 20 27 29
50 mV ac Magnetic Pickup
3
22 20 27 29
1 As defined by standard DIN 19234.
2 Add external resistor across field device for wire-off detection (0.4 mA) - (about 15
…20 K).
3 Add a jumper between 50 mV Sel and N (frequency - channel 0 = 4
to 6, channel 1 = 9 to 11;
gate - channel 0 = 21 to 23, channel 1 = 28
to 26).
4 Connect cable shields to shield busbar or shield terminating feedthroughs.
5 All GND terminals are internally connected together.
Channel 0 Relay Connections Channel 1 Relay Connections
COM 37 COM 46
N.O. 17 N.O. 31
N.C. 18 N.C. 32