FLEX Ex Frequency Input Module 9
Publication
1797-5.9 - June 2010
Wire to a 1797-TB3 or 1797-TB3S Terminal Base Unit
Connect wiring to the terminal base as shown below.
Wire the Module
Make wiring connections to the module terminal base unit according to the
wiring table below.
For VORTEX signals and magnetic pickups only.
Connect the channel ground terminals to the chassis ground terminals to
achieve the EMC protection class. Because, in this case, the intrinsically safe
circuit is grounded, and you must check the installation requirements of the
respective country for this context.
Make certain that you power this module with an intrinsically safe power
supply. Do not exceed the values listed in the specifications for this module.
If you connect or disconnect wiring while the field-side power is on, an
electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous
before proceeding.
Chassis
GND
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
16
35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
34
3V 6V V+ GND 50
mV
Sel
500/50
mV
3V6VV+GNDNN
Channel 0 Frequency Input Channel 1 Frequency Input
GND N N GND
Channel 0 Gate Input Channel 1 Gate Input
+V -V +V -V
Connections for Terminal Base 1797-TB3 shown
500/50
mV
50
mV
Sel
50
mV
Sel
500/50
mV
500/50
mV
50
mV
Sel
8V 8V
A
B
C
R0
COM
8V 8V
No connections allowed to terminals 19, 30, 36, 38, 39, 47, 48, 49
R1
NO
R1
NC
R0
NO
R0
NC
R1
COM
Chassis
GND