Rockwell-automation 1797-IJ2 FLEX Ex Frequency Input Module Instrukcja Użytkownika Strona 28

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 32
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 27
28 FLEX Ex Frequency Input Module
Publication
1797-5.9 - June 2010
Table 1
Table 2
Wiring
Method
Channel Terminals V
oc
(V)
I
sc
(mA)
V
t
(V) I
t
(mA)
Groups C
a
(F)
L
a
(mH)
1 and 2 Any one
channel
6, 7;
9, 8;
23, 24
26, 25
14.7 15.0 - - A, B 0.65 130.0
C, E 1.95 390.0
D, F, G 5.20 1040.0
1 and 2 Any one
channel
5, 3;
10, 12;
22, 20;
27, 29
14.7 10.0 - - A, B 0.65 300.0
C, E 1.95 900.0
D, F 5.20 2400.0
1 and 2 Any one
channel
5, 3, 6, 4;
10, 12, 9, 11;
22, 20, 21,
23;
27, 29, 26,
28
14.7 10.0 - - A 0.65 300.0
C, E 1.95 900.0
D, F, G 5.20 2400.0
1 and 2 Any one
channel
0, 2, 3;
1, 2, 3;
14, 12, 13;
15, 12, 13
26.5 82.0 - - A, B 0.13 4.5
C, E 0.39 13.5
D, F, G 1.04 36.0
Wiring
Method
Channel Terminals V
max
(V)
I
max
(mA)
Groups C
i
(F) L
i
(mH)
1 and 2 Any one
channel
17, 18, 37
or
31, 32, 46
28 93.0 A, B Negligible Negligible
C, E Negligible Negligible
D, F, G Negligible Negligible
Terminals V
t
(V) I
t
(mA) Groups C
a
(F) L
a
(H)
Male Bus
Connector
5.8 400 A-G 3.0 3.0