Publication 20P-IN004B-EN-P
12
Step 5C: Remove the 115V AC to 24V DC Converter Board
If the optional 115V AC to 24V DC converter board is not installed, continue
with Step 6: Remove the Existing Control Board
on page 13.
1. Remove the plug-in I/O terminal blocks.
2. Remove the two screws that secure the I/O converter board to the stand-offs
on the control board and remove the converter board.
3. Remove the two stand-offs and washers that support the converter board on
the control board.
Remove two screws
Tightening torque:
1.0 N•m (8.9 lb•in)
Remove two stand-offs
Tightening torque:
1.0 N•m (8.9 lb•in)