Publication 20P-IN004B-EN-P
Step 7: Install the New
Control Board
1. Install the new control board in the reverse order of removal as detailed in
Step 6: Remove the Existing Control Board
on page 13.
2. Verify that all DIP switch and jumper settings match those recorded in the
chart on page 13
. Refer to the PowerFlex DC Digital Drive User Manual,
publication 20P-UM001
, for detailed information on DIP switch and
jumper settings.
Step 8: Wire the Control
Board
Install the I/O and control wiring in reverse order of removal.
Figure 1 I/O and Control Wire Routing
Route I/O and control
wiring between
bottom front cover
and power terminal
cover/shield.
(Frame A shown)