Rockwell-automation 56AMXN/B ControlLogix AutoMax Comm Module Instrukcja Użytkownika Strona 47

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 46
AutoMax DCSNet/RE RIO Module Page 47
Publication number 56AMXN-UM002A-EN-P November 2002
For instance 2, the size must be 16 (8 words). The command writes to
the broadcast registers (32-39). Normally you would do this only as a
DCS master.
The maximum message size limits the number of attributes you can write
in a single message to 7.
DCS Raw Write, Service Code 32h
The DCS raw write command can be used to write a block of data to the
DCS data area on the module. You tell it the starting offset and the data
length and it writes the data. This is a very powerful command, use it
carefully!
Enter the following parameters in the MSG instruction tags:
Message
Type
CIP generic
Service Type Custom
Service Code 32h
Class (hex) C4h
Instance 1
Attribute (hex) Leave blank
Source
Element
Enter source tag
Source
Length (bytes)
2 + length of data in words * 2, max 480 (max data
length = 239)
Destination Enter destination tag name, not used but must be
entered
Table 16 DCS Data Object DCS Raw Write Parameters
In the source tag
First word offset in words = drop * 64 + register, range is 0 to 55 *
64 + 63 = 3583
Remaining
words
Data[…]
The module checks that the offset in in range and that the combination of
offset and length is in range. If this is not true, it returns an error.
Przeglądanie stron 46
1 2 ... 42 43 44 45 46 47 48 49 50 51 52 ... 71 72

Komentarze do niniejszej Instrukcji

Brak uwag