7-22 Communicating with Devices on a ControlNet Link
Determining the API
The API (actual packets per interval) is related to the RPI for the connection
and the NUT of the network. Use this table to select the API to enter in the
above worksheet:
Example 1: DriveLogix
Controller and Remote I/O
In the following example, one DriveLogix controller controls remote I/O
through a 1794-ACN15 module.
If: Enter this value for the API:
RPI NUT and RPI < 2NUT NUT
RPI 2NUT and RPI < 4NUT 2NUT
RPI 4NUT and RPI < 8NUT 4NUT
RPI 8NUT and RPI < 16NUT 8NUT
RPI 16NUT and RPI < 32NUT 16NUT
RPI 32NUT and RPI < 64NUT 32NUT
RPI 64NUT and RPI < 128NUT 64NUT
RPI 128NUT 128NUT
DriveLogix controller
(DriveLogix1)
ControlNet
1794-ACN with remote I/O
(Remote1)