Rockwell-automation 5720 DriveLogix System Instrukcja Użytkownika Strona 173

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 263
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 172
Publication 20D-UM002C-EN-P - November 2003
Communicating with Devices on a ControlNet Link 7-27
Example 2: Total connections required by DriveLogix1
The following table calculates the connections used in this example.
If you configured the local I/O modules as rack-optimized, you would only
need the DIN-rail connection to the I/O modules, reducing the above
example by 3 connections.
Connection: Amount:
DriveLogix1 controller to 3 local I/O modules
rack-optimized connection for the DIN rail
direct connection for each I/O module
1
3
DriveLogix1 controller to local 1788-CNC 0
DriveLogix1 controller to remote 1788-CNC 0
connected, cached MSG from DriveLogix1 to
DriveLogix2
1
produced TagA
produced from DriveLogix1 to DriveLogix2
other consumer (2 are configured)
1
1
consumed TagB 1
total connections used: 8
Przeglądanie stron 172
1 2 ... 168 169 170 171 172 173 174 175 176 177 178 ... 262 263

Komentarze do niniejszej Instrukcji

Brak uwag