7-18 Communicating with Devices on a ControlNet Link
Determining the API
The API (actual packets per interval) is related to the RPI for the connection
and the NUT of the network. Use this table to select the API to enter in the
above worksheet:
Example 1: DriveLogix
Controller and Remote I/O
In the following example, one DriveLogix5730 controller controls remote
I/O through a 1794-ACN15 module.
Example 1: Controlling Remote Devices
This example has DriveLogix1 controlling the I/O connected to the remote
1794-ACN15 module. The data the DriveLogix controller receives from the
remote I/O modules depends on how you configure the remote I/O modules.
You can configure each module as a direct connection or as rack optimized.
One chassis can have a combination of some modules configured as a direct
connection and others as rack optimized.
If: Enter this value for the API:
RPI NUT and RPI < 2NUT NUT
RPI 2NUT and RPI < 4NUT 2NUT
RPI 4NUT and RPI < 8NUT 4NUT
RPI 8NUT and RPI < 16NUT 8NUT
RPI 16NUT and RPI < 32NUT 16NUT
RPI 32NUT and RPI < 64NUT 32NUT
RPI 64NUT and RPI < 128NUT 64NUT
RPI 128NUT 128NUT
ahw0933.eps
DriveLogix5730 Controller
(DriveLogix1)
1794-ACN with remote I/O
(Remote1)
ControlNet