A-4 DriveLogix5730 Controller Specifications
Indicator: Color: Description:
RUN off The controller is in Program or Test mode.
solid green The controller is in Run mode.
FORCE off No tags contain I/O force values.
I/O forces are inactive (disabled).
solid amber I/O forces are active (enabled).
I/O force values may or may not exist.
flashing amber One or more input or output addresses have been forced to an On or Off
state, but the forces have not been enabled.
BAT off The battery supports memory.
solid red Either the battery is:
not installed.
95% discharged and should be replaced.
I/O off Either:
There are no devices in the I/O configuration of the controller.
The controller does not contain a project (controller memory is empty).
solid green The controller is communicating with all the devices in its I/O configuration.
flashing green One or more devices in the I/O configuration of the controller are not
responding.
flashing red The controller is not communicating to any devices.
The controller is faulted.
COM off No RS-232 activity.
flashing green RS-232 activity.
OK off No power is applied.
flashing red If the controller is:
a new controller
not a new controller
Then:
the controller requires a firmware update
A major fault occurred.
To clear the fault, either:
- Turn the key switch from PROG to RUN to PROG
- Go online with RSLogix 5000 software
solid red The controller detected a non-recoverable fault, so it cleared the project
from memory. To recover:
Cycle power to the chassis.
Download the project.
Change to Run mode.
If the OK LED remains solid red, contact your Rockwell Automation
representative or local distributor.
solid green Controller is OK.
flashing green The controller is storing or loading a project to or from nonvolatile memory.